wago10117The current and voltage tap complements the Wago portfolio of current and energy measurement technology: the combination of 2-wire through terminal and current and voltage tap forms the ideal basis for successful energy management - because it is wherever electrical power is to be measured Current and voltage required.

The current and voltage tap with 95 mm² has the same width as the 2 conductor feed-through terminal and can be quickly and easily plugged into the jumper slot. The end customer can tap the energy data directly at the feed and thus requires no further converters or mounting units.

In addition, the power and voltage tap has an integrated fuse with detector. This provides reliable protection for downstream energy meters. If the fuse fails due to an insulation fault, a disconnection from the mains is ensured. A likewise integrated current transformer with a conversion ratio 250 A / 1 A enables a precise current measurement according to EN 61869-2 - in the accuracy class 0,5. The connection of the current output is marked with S1 (black) and S2 (red). A handle operation is used to connect and disconnect fine-stranded conductors. The 5 pole design (2 x S1 and 3 x S2) offers advantages such as short-circuiting the current transformer (S1 and S2) via a jumper (2000-402) or direct star point bridging on the current transformer. The voltage is tapped via a redundant connection terminal.